The medical gas wall outlet shall be Ohio Medicaf Series. The outlet shall be UL* Listed, NFPA994* compliant, cleaned for medical gas service, and be pressure tested. Each oulet shall have less than 3 psi (21 kPa) pressure drop through the oulet @ 120 L/min, and 50 psi (345 kPa) inlet pressure. For outlets providing positive pressure gas, the outlet shall be equipped with a primary and secondary check valve, the secondary check valve shall be rated for 200 psi (1,379 kPa) allowing the primary check valve to be removed for service without isolating the entire zone.